Galaxy VX

480 V UPS System

Schneider Electric

Galaxy VX - Schneider Electric

Galaxy VX 480 V UPS System Technical Specifications 07/2020 www.schneider-electric.com

Electrical equipment should only be installed, operated, serviced, and maintained by qualified personnel. No responsibility is assumed by Schneider Electric ...

Jul 1, 2020 — Electrical equipment should only be installed, operated, serviced, and maintained by qualified personnel. No responsibility is assumed by Schneider Electric ...

PDF 990-5451F-EN new
Galaxy VX
480 V UPS System Technical Specifications
07/2020
www.schneider-electric.com

Legal Information
The Schneider Electric brand and any trademarks of Schneider Electric SE and its subsidiaries referred to in this guide are the property of Schneider Electric SE or its subsidiaries. All other brands may be trademarks of their respective owners. This guide and its content are protected under applicable copyright laws and furnished for informational use only. No part of this guide may be reproduced or transmitted in any form or by any means (electronic, mechanical, photocopying, recording, or otherwise), for any purpose, without the prior written permission of Schneider Electric. Schneider Electric does not grant any right or license for commercial use of the guide or its content, except for a non-exclusive and personal license to consult it on an "as is" basis. Schneider Electric products and equipment should be installed, operated, serviced, and maintained only by qualified personnel. As standards, specifications, and designs change from time to time, information contained in this guide may be subject to change without notice. To the extent permitted by applicable law, no responsibility or liability is assumed by Schneider Electric and its subsidiaries for any errors or omissions in the informational content of this material or consequences arising out of or resulting from the use of the information contained herein.
Go to: https://www.productinfo.schneider-electric.com/galaxyvx_ul/ or scan the QR code above for digital experience and translated manuals.

Table of Contents

480 V UPS System

990-5451F-001

Important Safety Instructions -- SAVE THESE INSTRUCTIONS .........................................................................................5
FCC Statement ..........................................................................................6 Safety Precautions .....................................................................................6
Technical Data.............................................................................................8
System Overview .......................................................................................8 Model List ..................................................................................................9 Overview of Configurations .......................................................................10
Overview of UPSs with 1250 kW I/O Cabinet - Single Utility/ Mains................................................................................................. 11 Overview of UPSs with 1250 kW I/O Cabinet - Dual Utility/Mains ............ 11 Overview of UPS with Remote Maintenance Bypass Cabinet ­ Dual Utility/Mains System............................................................................12 Overview of UPSs with 1500 kW I/O Cabinet ­ Single Utility/ Mains ................................................................................................. 12 Overview of UPSs with 1500 kW I/O Cabinet ­ Dual Utility/Mains ...........13 Input Power Factor ...................................................................................13 Input Voltage Window ...............................................................................14 Inverter Short-Circuit Capabilities (Bypass not Available).............................14 Efficiency for UPSs with 1250 kW I/O Cabinet.............................................15 Efficiency for UPSs with 1500 kW I/O Cabinet.............................................17 Derating Due to Load Power Factor ...........................................................17 Batteries ..................................................................................................18 Battery Runtimes for Li-Ion Battery Cabinets LIBATTSMGGIEC .............18 Typical Battery Runtimes for Classic Battery Cabinets ...........................20 End of Discharge Voltage ....................................................................20 Battery Voltage Range ........................................................................21 Compliance .............................................................................................. 21 Communication and Management .............................................................21 EPO Connections ...............................................................................22 Overview of Input Contacts and Output Relays......................................22
Facility Planning ........................................................................................24
Specifications for 500 kW UPS ..................................................................24 Specifications for 625 kW UPS ..................................................................26 Specifications for 750 kW UPS ..................................................................28 Specifications for 800 kW UPS ..................................................................30 Specifications for 1000 kW UPS ................................................................32 Specifications for 1100 kW UPS.................................................................34 Specifications for 1250 kW UPS ................................................................36 Specifications for 1500 kW UPS ................................................................38 Recommended Upstream Protection and Cable Sizes ­ UL .........................39 Recommended Bolt and Lug Sizes for Copper Cables.................................41 Recommended Bolt and Lug Sizes for Aluminium Cables ............................42 Weights and Dimensions...........................................................................42
Weights and Dimensions for UPSs with 1250 kW I/O Cabinet.................42 Weights and Dimensions for UPSs with 1500 kW I/O Cabinet.................43 Maintenance Bypass Cabinet Weights and Dimensions .........................43 Clearance ................................................................................................43
3

480 V UPS System

Clearance for UPSs with 1250 kW I/O Cabinet ......................................43 Clearance for UPSs with 1500 kW I/O Cabinet ......................................44 Guidance for Organizing Battery Cables.....................................................44 Environment............................................................................................. 45 Heat Dissipation (BTU/hr) for UPSs with 1250 kW I/O Cabinet .....................45 Heat Dissipation (BTU/hr) for UPSs with 1500 kW I/O Cabinet .....................48
Options .......................................................................................................50
Hardware Options.....................................................................................50 Configuration Options ...............................................................................50
Limited Factory Warranty.........................................................................51

4

990-5451F-001

Important Safety Instructions -- SAVE THESE INSTRUCTIONS

480 V UPS System

Important Safety Instructions -- SAVE THESE INSTRUCTIONS

Read these instructions carefully and look at the equipment to become familiar with it before trying to install, operate, service or maintain it. The following safety messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of this symbol to a "Danger" or "Warning" safety message indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages with this symbol to avoid possible injury or death.

DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury. Failure to follow these instructions will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury. Failure to follow these instructions can result in death, serious injury, or equipment damage.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. Failure to follow these instructions can result in injury or equipment damage.
NOTICE
NOTICE is used to address practices not related to physical injury. The safety alert symbol shall not be used with this type of safety message. Failure to follow these instructions can result in equipment damage.

Please Note

Electrical equipment should only be installed, operated, serviced, and maintained by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction, installation, and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved.

990-5451F-001

5

480 V UPS System
FCC Statement

Important Safety Instructions -- SAVE THESE INSTRUCTIONS
NOTE: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. Any changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment.

Safety Precautions
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH · The product must be installed according to the specifications and
requirements as defined by Schneider Electric. It concerns in particular the external and internal protections (upstream circuit breakers, battery circuit breakers, cabling, etc.) and environmental requirements. No responsibility is assumed by Schneider Electric if these requirements are not respected. · After the UPS system has been electrically wired, do not start up the system. Start-up must only be performed by Schneider Electric. Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The UPS System must be installed according to local and national regulations. Install the UPS according to: · IEC 60364 (including 60364­4­41- protection against electric shock, 60364­
4­42 - protection against thermal effect, and 60364­4­43 - protection against overcurrent), or · NEC NFPA 70 depending on which one of the standards apply in your local area.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH · Install the UPS system in a temperature controlled area free of conductive
contaminants and humidity. · Install the UPS system on a non-inflammable, level, and solid surface (e.g.
concrete) that can support the weight of the system. Failure to follow these instructions will result in death or serious injury.

6

990-5451F-001

Important Safety Instructions -- SAVE THESE INSTRUCTIONS

480 V UPS System

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The UPS is not designed for and must therefore not be installed in the following unusual operating environments: · Damaging fumes · Explosive mixtures of dust or gases, corrosive gases, or conductive or
radiant heat from other sources · Moisture, abrasive dust, steam or in an excessively damp environment · Fungus, insects, vermin · Salt-laden air or contaminated cooling refrigerant · Pollution degree higher than 2 according to IEC 60664-1 · Exposure to abnormal vibrations, shocks, and tilting · Exposure to direct sunlight, heat sources, or strong electromagnetic fields Failure to follow these instructions will result in death or serious injury.

NOTICE
RISK OF OVERHEATING
Respect the clearance requirements around the UPS system and do not cover the product's ventilation openings when the UPS system is in operation.
Failure to follow these instructions can result in equipment damage.

NOTICE
RISK OF EQUIPMENT DAMAGE
Do not connect the UPS output to regenerative load systems including photovoltaic systems and speed drives.
Failure to follow these instructions can result in equipment damage.

990-5451F-001

7

480 V UPS System
Technical Data

Technical Data

System Overview
Each Galaxy VX UPS consists of the following components: · An I/O cabinet for wield wiring containing the static switch, a backfeed protection switch, and the user interface. · A number of 250 kW power cabinets containing the power electronics.
UPSs with 1250 kW I/O Cabinet
The 1250 kW I/O cabinet is used for UPS systems from a minimum configuration of 500 kW with two power cabinets to a maximum configuration of 1250 kW N+1 with six power cabinets. The I/O cabinet is placed to the left and two to six power cabinets (depending on system size) are placed to the right. The image below shows the maximum configuration.

UPSs with 1500 kW I/O Cabinet
The 1500 kW I/O cabinet is used for UPS systems from a minimum configuration of 500 kW with two power cabinets to a maximum configuration of 1500 kW N+1 with seven power cabinets. The image below shows the maximum configuration.

Maintenance Bypass Cabinet for UPSs with a Maximum Rating of 750 kW
The maintenance bypass cabinet contains the following breakers to isolate the UPS during maintenance:

8

990-5451F-001

Technical Data

· Static switch input breaker (SSIB) · Maintenance bypass breaker (MBB) · Unit output breaker (UOB)
Maintenance Bypass Cabinet

480 V UPS System

Model List
UPSs with 1250 kW I/O Cabinet
· GVX500K500NGS: Galaxy VX 500 kW, 480 V, start-up 5x8 · GVX500K750NGS: Galaxy VX 500 kW scalable to 750 kW 480 V, start-up
5x8 · GVX500K1000NGS: Galaxy VX 500 kW scalable to 1000 kW 480 V, start-up
5x8 · GVX500K1250NGS: Galaxy VX 500 kW scalable to 1250 kW 480 V, start-up
5x8 · GVX625K625NGS: Galaxy VX 625 kW, 480 V, start-up 5x8 · GVX625K1000NGS: Galaxy VX 625 kW scalable to 1000 kW 480 V, start-up
5x8 · GVX750K500NGS: Galaxy VX 500 kW N+1 redundant UPS 480 V, start-up
5x8 · GVX750K750NGS: Galaxy VX 750 kW, 480 V, start-up 5x8
· GVX750K1000NGS: Galaxy VX 750 kW scalable to 1000 kW 480 V, start-up 5x8
· GVX750K1250NGS: Galaxy VX 750 kW scalable to 1250 kW 480 V, start-up 5x8
· GVX800K800NGS: Galaxy VX 800 kW, 480 V, start-up 5x8
· GVX1000K750NGS: Galaxy VX 750 kW N+1 redundant UPS 480 V, start-up 5x8
· GVX1000K1000NGS: Galaxy VX 1000 kW, 480 V, start-up 5x8 · GVX1000K1250NGS: Galaxy VX 1000 kW scalable to 1250 kW 480 V, start-
up 5x8 · GVX1100K1100NGS: Galaxy VX 1100 kW, 480 V, Start-up 5x8 · GVX1250K1000NGS: Galaxy VX 1000 kW N+1 redundant UPS 480 V, start-
up 5x8 · GVX1250K1250NGS: Galaxy VX 1250 kW, 480 V, start-up 5x8
· GVX1500K1100NGS: Galaxy VX 1100 kW N+1 Redundant UPS 480 V, Start up 5x8
· GVX1500K1250NGS: Galaxy VX 1250 kW N+1 Redundant UPS 480 V, startup 5x8

990-5451F-001

9

480 V UPS System

Technical Data

UPSs with 1500 kW I/O Cabinet
· GVX500K1500GS: Galaxy VX 500 kW 480 V scalable to 1500 kW, start-up 5x8
· GVX750K1500GS: Galaxy VX 750 kW 480 V scalable to 1500 kW, start-up 5x8
· GVX1000K1500GS:Galaxy VX 1000 kW scalable to 1500 kW 480 V, start-up 5x8
· GVX1250K1500GS: Galaxy VX 1250 kW scalable to 1500 kW 480 V, start-up 5x8
· GVX1500K1500GS: Galaxy VX 1500 kW 480 V, start-up 5x8
· GVX1750K1500GS: Galaxy VX 1500 kW N+1 Redundant UPS 480 V, startup 5x8

Maintenance Bypass Cabinets
· GVXMBCR625KG: Galaxy VX 625 kW 480 V remote maintenance bypass cabinet
· GVXMBCR750KG: Galaxy VX 750 kW 480 V remote maintenance bypass cabinet

Overview of Configurations

Breakers in the System

UIB SSIB BB MBB UOB BF2

Unit input breaker Static switch input breaker Battery breaker Maintenance bypass breaker Unit output breaker Backfeed protection switch

10

990-5451F-001

Technical Data

480 V UPS System

Overview of UPSs with 1250 kW I/O Cabinet - Single Utility/Mains
The illustration shows a 750 kW UPS. The principle is the same for the other UPSs with the 1250 kW I/O cabinet.

Overview of UPSs with 1250 kW I/O Cabinet - Dual Utility/Mains
The illustration shows a 750 kW UPS. The principle is the same for the other UPSs with the 1250 kW I/O cabinet.

990-5451F-001

11

480 V UPS System

Technical Data

Overview of UPS with Remote Maintenance Bypass Cabinet ­ Dual Utility/Mains System

Overview of UPSs with 1500 kW I/O Cabinet ­ Single Utility/Mains
The illustration shows a 1500 kW UPS. The principle is the same for the other UPSs with the 1500 kW I/O cabinet.
Galaxy VX 1500 kW UPS

12

990-5451F-001

Technical Data

480 V UPS System

Overview of UPSs with 1500 kW I/O Cabinet ­ Dual Utility/Mains
The illustration shows a 1500 kW UPS. The principle is the same for the other UPSs with the 1500 kW I/O cabinet.

Galaxy VX 1500 kW UPS

Input Power Factor

25% load 50% load 75% load 100% load

500 kW 0.98 0.99 0.99 0.99

625 kW 0.98 0.99 0.99 0.99

750 kW 0.98 0.99 0.99 0.99

800 kW 0.98 0.99 0.99 0.99

1000 kW 0.98 0.99 0.99 0.99

1100 kW 0.98 0.99 0.99 0.99

1250 kW 0.98 0.99 0.99 0.99

1500 kW 0.98 0.99 0.99 0.99

990-5451F-001

13

480 V UPS System
Input Voltage Window

Technical Data

Inverter Short-Circuit Capabilities (Bypass not Available)
IK1 ­ Short-Circuit between a Phase and Neutral

14

990-5451F-001

Technical Data
IK2 ­ Short-Circuit between Two Phases

480 V UPS System

IK3 ­ Short-Circuit between All Three Phases

Efficiency for UPSs with 1250 kW I/O Cabinet

Efficiency for a 500 kW UPS

25% load 50% load 75% load 100% load

Normal operation 94.9% 95.9% 96.0% 95.9%

ECO mode 97.3% 98.4% 98.8% 99.0%

ECOnversion 96.9% 98.2% 98.7% 98.9%

Battery operation 96.6% 96.7% 96.3% 95.9%

990-5451F-001

15

480 V UPS System

Efficiency for a 625 kW UPS

25% load 50% load 75% load 100% load

Normal operation 95.0% 96.2% 96.3% 96.2%

Efficiency for a 750 kW UPS

25% load 50% load 75% load 100% load

Normal operation 95.4% 96.1% 96.0% 95.8%

Efficiency for an 800 kW UPS

25% load 50% load 75% load 100% load

Normal operation 95.2% 96.2% 96.1% 96.3%

Efficiency for a 1000 kW UPS

25% load 50% load 75% load 100% load

Normal operation 95.6% 96.3% 96.2% 96.0%

Efficiency for a 1100 kW UPS

25% load 50% load 75% load 100% load

Normal operation 95.8% 96.4% 96.3% 96.1%

Efficiency for a 1250 kW UPS

25% load 50% load 75% load 100% load

Normal operation 95.8% 96.4% 96.2% 96.0%

ECO mode 97.5% 98.6% 98.8% 99.0%
ECO mode 97.9% 98.6% 98.8% 98.9%
ECO mode 98.7% 98.9% 98.9% 99.0%
ECO mode 98.1% 98.8% 99.0% 99.1%
ECO mode 98.3% 98.9% 99.0% 99.1%
ECO mode 98.3% 98.9% 99.1% 99.1%

16

Technical Data

ECOnversion 97.1% 98.4% 98.7% 98.9%

Battery operation 96.6% 96.7% 96.3% 95.9%

ECOnversion 97.7% 98.5% 98.7% 98.9%

Battery operation 96.5% 96.6% 96.2% 95.8%

ECOnversion 97.4% 98.5% 98.8% 99.1%

Battery operation 98.9% 96.6% 96.8% 96.3%

ECOnversion 97.9% 98.7% 98.9% 99.1%

Battery operation 96.6% 96.7% 96.3% 95.9%

ECOnversion 97.8% 98.7% 98.9% 99.0%

Battery operation 97.8% 98.7% 98.9% 99.0%

ECOnversion 97.9% 98.7% 99.0% 99.1%

Battery operation 96.6% 96.6% 96.3% 96.1%
990-5451F-001

Technical Data

Efficiency for UPSs with 1500 kW I/O Cabinet

Efficiency for a 500 kW UPS

25% load 50% load 75% load 100% load

Normal operation 95.8% 96.4% 96.2% 96.1%

ECO mode 98.5% 99.1% 99.2% 99.2%

ECOnversion 98.2% 99.1% 99.2% 99.2%

Efficiency for a 750 kW UPS

25% load 50% load 75% load 100% load

Normal operation 95.9% 96.5% 96.3% 96.0%

ECO mode 98.5% 99.1% 99.2% 99.2%

ECOnversion 98.2% 99.0% 99.2% 99.2%

Efficiency for a 1000 kW UPS

25% load 50% load 75% load 100% load

Normal operation 95.9% 96.5% 96.4% 95.9%

ECO mode 98.6% 99.1% 99.2% 99.2%

ECOnversion 98.2% 99.0% 99.2% 99.2%

Efficiency for a 1250 kW UPS

25% load 50% load 75% load 100% load

Normal operation 96.0% 96.6% 96.4% 96.0%

ECO mode 98.7% 99.2% 99.3% 99.3%

ECOnversion 98.3% 99.1% 99.3% 99.3%

Efficiency for a 1500 kW UPS

25% load 50% load 75% load 100% load

Normal operation 96.0% 96.5% 96.3% 96.0%

ECO mode 98.7% 99.1% 99.3% 99.3%

ECOnversion 98.3% 99.1% 99.3% 99.3%

Derating Due to Load Power Factor
0.7 leading to 0.5 lagging without derating.

480 V UPS System
Battery operation 95.9% 96.4% 96.0% 95.6%
Battery operation 95.9% 96.4% 96.0% 95.6%
Battery operation 95.9% 96.4% 96.0% 95.6%
Battery operation 95.9% 96.4% 96.0% 95.6%
Battery operation 95.9% 96.4% 96.1% 95.7%

990-5451F-001

17

480 V UPS System

Technical Data

Batteries

Battery Runtimes for Li-Ion Battery Cabinets LIBATTSMGGIEC

500 kW UPS

NOTE: Please allow for a tolerance of ±10% at the beginning of life.
The estimated battery runtimes are based on an environment with an ambient temperature of 23 °C (75 °F).

Number of LIBATTSMGGIEC cabinets
25% load
50% load
75% load
100% load

3
46:30 23:00 14:30 10:30

4
62:30 31:00 20:00 14:30

5
78:30 39:00 25:30 18:30

6
94:30 47:00 31:00 22:30

7

8

9

10

11

12

110:00 55:00 36:00 27:00

125:00 63:00 41:30 31:00

140:00 71:00 47:00 35:00

155:00 79:00 52:00 39:00

170:00 87:00 57:30 43:00

185:00 95:00 63:00 46:30

625 kW UPS

Number of LIBATTSMGGIEC cabinets
25% load
50% load
75% load
100% load

3
37:00 18:00 11:30 5:051

4
49:30 24:30 16:00 11:30

5
62:30 31:00 20:00 14:30

6
75:00 37:30 24:30 18:00

7
88:00 43:30 29:00 21:00

8

9

10

11

12

100:00 50:00 33:00 24:30

110:00 56:30 37:30 27:30

125:00 63:00 41:30 31:00

135:00 69:30 46:00 34:00

150:00 76:00 50:00 37:00

750 kW UPS

Number of LIBATTSMGGIEC cabinets
25% load
50% load
75% load
100% load

4
41:30 20:00 13:00 9:301

5
52:00 25:30 16:30 12:00

6
63:00 31:00 20:00 14:30

7
73:30 36:30 23:30 17:30

8
84:00 41:30 27:30 20:00

9
94:30 47:00 31:00 22:30

10

11

12

105:00 52:30 34:30 25:30

115:00 57:30 38:00 28:00

125:00 63:00 41:30 31:00

1. Only partial discharge 18

990-5451F-001

Technical Data

800 kW UPS

Number of LIBATTSMGGIEC cabinets
25% load
50% load
75% load
100% load

4
39:00 19:00 12:00 7:452

1000 kW UPS

Number of LIBATTSMGGIEC cabinets
25% load
50% load
75% load
100% load

5
39:00 19:00 12:00 7:352

1100 kW UPS

Number of LIBATTSMGGIEC cabinets
25% load
50% load
75% load
100% load

5
35:00 17:00 11:00 1:002

1250 kW UPS

Number of LIBATTSMGGIEC cabinets
25% load
50% load
75% load
100% load

6
37:30 18:00 11:30 5:052

1500 kW UPS

Number of LIBATTSMGGIEC cabinets
25% load
50% load
75% load
100% load

7
36:30 17:30 11:00 2:252

480 V UPS System

5

6

7

8

9

10

11

12

49:00 24:00 15:30 11:00

59:00 29:00 19:00 14:00

69:00 34:00 22:00 16:30

79:00 39:00 25:30 19:00

88:30 44:00 29:00 21:30

98:30 49:00 32:30 24:00

105:00 54:30 35:30 26:30

115:00 59:30 39:00 29:00

6
47:00 23:00 15:00 10:30

7
55:00 27:00 17:30 12:30

8
63:00 31:00 20:00 14:30

9
71:00 35:00 23:00 16:30

10
79:00 39:00 25:30 18:30

11
87:00 43:00 28:00 20:30

12
95:00 47:00 31:00 22:30

6
42:30 21:00 13:30 9:502

7
50:00 24:30 16:00 11:30

8
57:00 28:00 18:00 13:30

9
64:30 32:00 20:30 15:00

10
71:30 35:30 23:00 17:00

11
79:00 39:00 25:30 19:00

12
86:00 43:00 28:00 20:30

7
43:30 21:30 13:30 10:00

8
50:00 24:30 16:00 11:30

9
56:30 28:00 18:00 13:00

10
63:00 31:00 20:00 14:30

11
69:30 34:00 22:30 16:30

12
76:00 37:30 24:30 18:00

8
41:30 20:00 13:00 9:302

9
47:00 23:00 14:30 10:30

10
52:30 25:30 16:30 12:00

11
57:30 28:30 18:30 13:30

12
63:00 31:00 20:00 14:30

13
68:30 33:30 22:00 16:00

2. Only partial discharge

990-5451F-001

19

480 V UPS System

1500 kW UPS

Number of LIBATTSMGGIEC cabinets
25% load
50% load
75% load
100% load

14
73:30 36:30 23:30 17:30

15
79:00 39:00 25:30 18:30

16
84:00 41:30 27:00 20:00

17
89:30 44:30 29:00 21:30

18
94:30 47:00 30:30 22:30

Technical Data

19
100:00 49:30 32:30 24:00

20
105:00 52:30 34:30 25:30

Typical Battery Runtimes for Classic Battery Cabinets

Part Number

Battery

GVXCBC400E490 C&D GVXCBC400E540 GVXCBC600E490 GVXCBC600E540 GVXCBC400P505 Enersys GVXCBC400P540 GVXCBC600P505 GVXCBC600P540

Description
400 A and 490 watt/ cell batt
400 A and 540 watt/ cell batt
600 A and 490 watt/ cell batt
600 A and 540 watt/ cell batt
400 A and 505 watt/ cell batt
400 A and 540 watt/ cell batt
600 A and 505 watt/ cell batt
600 A and 540 watt/ cell batt

500 kW
Runtime3
3 battery cabinets: 7 min 09 sec
3 battery cabinets: 8 min 56 sec
3 battery cabinets: 7 min 09 sec
3 battery cabinets: 8 min 56 sec
3 battery cabinets: 8 min 19 sec
3 battery cabinets: 9 min 18 sec
3 battery cabinets: 8 min 19 sec
3 battery cabinets: 9 min 18 sec

625 kW
4 battery cabinets: 8 min 28 sec NA
4 battery cabinets: 8 min 28 sec 3 battery cabinets: 5 min 37 sec NA
NA
3 battery cabinets: 5 min 28 sec 3 battery cabinets: 6 min 18 sec

750 kW
4 battery cabinets: 5 min 26 sec
4 battery cabinets: 7 min 08 sec
4 battery cabinets: 5 min 26 sec
4 battery cabinets: 7 min 08 sec
4 battery cabinets: 6 min 46 sec
4 battery cabinets: 7 min 40 sec
4 battery cabinets: 6 min 46 sec
4 battery cabinets: 7 min 40 sec

End of Discharge Voltage
The voltage is 1.6 to 1.75 per cell depending on discharge ratio.

3. Based on max. 2% voltage drop and 100% load 20

990-5451F-001

Technical Data
Battery Voltage Range

480 V UPS System

Compliance
Safety EMC/EMI/RFI Performance Markings Transportation Seismic zone

UL 1778 5th edition FCC 15B, class A IEC62040­3 UL1778 Listing and CSA C22.2 NO.107.3 IEC 60721-4-2 Level 2M2 OSHPD, IBC2012 and CBC2013 to SDS = 1.83 g

Communication and Management

Local Area Network Extensions MODBUS Relay outputs Dry contact inputs Standard control panel Audible alarm Emergency Power Off (EPO)
External switchgear

100 Mbps
Two optional Network Management Cards
MODBUS TCP/IP 6 configurable
5 configurable
7" touch-screen display
Yes Options:
· Normally Open (NO) · Normally Closed (NC) · External 24 VDC SELV Option containing: · Unit Input Breaker (UIB) · Unit Output Breaker (UOB)

990-5451F-001

21

480 V UPS System
External synchronization Battery monitoring
EPO Connections

· Static Switch Input Breaker (SSIB) · Maintenance Bypass Breaker (MBB) · System Isolation Breaker (SIB)
Yes
Yes -- string level breaker monitoring

Technical Data

Overview of Input Contacts and Output Relays
Input Contacts
Do not connect any circuit to the input contacts unless it can be confirmed that the circuit is Class 2/SELV.
All circuits connected must have the same 0 V reference.
The switch SW5500 on 0P6548 is used to select between internal SELV supply for inputs (standard setting) and external supply4. If external supply is selected, the supply must be connected to J5530.

Name IN 1 (Contact 1) IN 2 (Contact 2) IN 3 (Contact 3) IN 4 (Contact 4) IN 5 (Contact 5) IN 6 IN 7 IN 8 IN 9 IN 10 IN 11 IN 14

Description Configurable input contact Configurable input contact Configurable input contact Configurable input contact Configurable input contact UOB redundant AUX contact Transformer temperature switch External bonding contact Forced external synchronization input External synchronization requested Use static bypass standby MegaTie

Location 0P6548 terminal J55025 0P6548 terminal J55035 0P6548 terminal J55045 0P6548 terminal J55055 0P6548 terminal J55105 0P6548 terminal J55095 0P6548 terminal J55085 0P6548 terminal J55075 0P6548 terminal J55065 0P6548 terminal J55115 0P6548 terminal J55125 0P6552 terminal J90275

4. An external supply is useful in parallel systems where inputs are connected between different UPSs. This is to have a common reference and to avoid cross currents.
5. Class 2/SELV wiring

22

990-5451F-001

Technical Data

480 V UPS System
Output Relays
NOTE: Maximum 250 VAC 5 A must be connected to the output relays. All external circuitry must be fused with maximum 5 A fast acting fuses.

Name OUT 1 (Relay 1) OUT 2 (Relay 2) OUT 3 (Relay 3) OUT 4 OUT 5 OUT 6 OUT 7 OUT 8 (Relay 4) OUT 9 (Relay 5) OUT 10 (Relay 6) OUT 14

Description Configurable output relay Configurable output relay Configurable output relay Forced external synchronization output MegaTie External synchronization requested output UPS in inverter ON Configurable output relay Configurable output relay Configurable output relay Bonding contactor

Location 0P6547 terminal J4939 0P6547 terminal J4940 0P6547 terminal J4941 0P6548 terminal J55206 0P6548 terminal J55216 0P6548 terminal J55226 0P6548 terminal J55236 0P6548 terminal J55246 0P6548 terminal J55256 0P6548 terminal J55286 0P6552 terminal J90296

NOTE: Refer to the operation manual for configuration options.

6. Class 2/SELV wiring

990-5451F-001

23

480 V UPS System
Facility Planning

Facility Planning

Specifications for 500 kW UPS

Input Specifications

Voltage (V) Connections
Input voltage range (V)9 Frequency (Hz) Nominal input current (A) Maximum input current (A)10 Input current limitation (A) Total harmonic distortion (THDI) Input power factor Protection Ramp-in Connections
Bypass voltage range (V) Frequency (Hz) Frequency range (Hz) Nominal bypass current (A) Maximum short circuit rating Thyristor I²t (kA*s²)
BF2 magnetic trip Protection

380

400

415

440 V

480 V

IEC: L1, L2, L3, PE 7 UL: L1, L2, L3 + G 8

340-456

340-480

353-498

374-528

408-576

40-70

800

760

731

685

633

886

851

819

767

728

890

832

760

<3% at 100% load, <4% at 50% load, <9% at 25% load

0.99 at >40% load, 0.98 at >20% load, 0.97 at >10% load

Contactors Adaptive 1-300 seconds

IEC: L1, L2, L3, N, PE or L1, L2, L3, PE 11 UL: L1, L2, L3, G or L1, L2, L3, N, G

342-418

360-440

374-457

396-484

432-528

50 or 60

Programmable: ±0.1, ±3, ±10. Default is ±3

767

729

703

663

606

100 kA RMS (conditioned by an internal molded switch with 90 kA peak magnetic trip)

9680 (1250 kW I/O) 16245 (1500 kW I/O)

9165 (1250 kW I/O) 16245 (1500 kW I/O)

39 kA

Molded switch with trip for backfeed protection

Bypass Specifications

7. TN, TT, and IT power distribution systems are supported. 8. WYE source ­ solid grounded and high resistance grounded sources are supported. Corner (line) grounding is not supported. 9. The system can operate at 600 V for 1 minute. 10. At nominal input voltage and full charge. 11. TN, TT, and IT power distribution systems with no earthed line conductors are supported.

24

990-5451F-001

Facility Planning

480 V UPS System

Output Specifications

Voltage (V)

380

400

415

440 V

480 V

Connections

IEC: L1, L2, L3, N, PE or L1, L2, L3, PE UL: L1, L2, L3, G, GEC12 or L1, L2, L3, N, G

Overload capacity

Normal operation: 150% for 1 minute, 125% for 10 minutes Battery operation: 115% for 1 minute Bypass operation: 110%13 continuous, 1000% for 60 milliseconds for systems with 1250 kW I/O cabinet and 100 milliseconds for systems with 1500 kW I/O cabinet

Output voltage tolerance

Balanced load: ±1%, Unbalanced load: ±3%

Dynamic load response

±5% after 2 ms, ±1% after 50 ms

Output power factor

1

Nominal output current (A)

760

722

696

656

601

Total harmonic distortion (THDU)

<2% at 100% linear load, <3% at 100% non-linear load

Output frequency (Hz)

50/60 (synchronized to bypass), 50/60 Hz ±0.1% (free-running)

Slew rate (Hz/sec)

Programmable: 0.25, 0.5, 1, 2, 4, 6

Output performance classification (according to IEC/ EN62040-3)

Double-conversion: VFI-SS-111

Load crest factor

Up to 3 (THDU < 5%)

Load power factor

0.7 leading to 0.5 lagging without derating

Charging power in % of output power Maximum charging power (kW) Nominal battery voltage (VDC)

35% at  80% load, 12% at 100% load 60 at 100% load, 175 at <80% load 480

40% at  80% load, 15% at 100% load
75 at 100% load, 200 at 80% load

Nominal float voltage (VDC)

546

End of discharge voltage (full load) (VDC) 384

End of discharge voltage (no load) (VDC) 420

Battery current at full load and nominal battery voltage (A)

1090

Battery current at full load and minimum battery voltage (A)

1362

Maximum battery backup time

Unlimited

Temperature compensation (per cell)

-3.3 mV per °C for T  25 °C, 0 mV per °C for T < 25 °C

Ripple current

< 5% C20 (5 minutes backup time)

Battery test

Manual/automatic (selectable)

Deep discharge protection

Yes

Recharge according to battery temperature Yes

Battery Specifications

12. Per NEC 250.30. 13. 125% for 480 V.

990-5451F-001

25

480 V UPS System
Specifications for 625 kW UPS

Facility Planning

Input Specifications

Bypass Specifications

Voltage (V) Connections
Input voltage range (V)16 Frequency (Hz) Nominal input current (A) Maximum input current (A)17 Input current limitation (A) Total harmonic distortion (THDI) Input power factor Protection Ramp-in Connections
Bypass voltage range (V) Frequency (Hz) Frequency range (Hz) Nominal bypass current (A) Maximum short circuit rating Thyristor I²t (kA*s²) BF2 magnetic trip Protection Connections
Overload capacity
Output voltage tolerance Dynamic load response Output power factor Nominal output current (A) Total harmonic distortion (THDU) Output frequency (Hz) Slew rate (Hz/sec) Output performance classification (according to IEC/ EN62040-3) Load crest factor Load power factor

380

400

415

440 V

480 V

IEC: L1, L2, L3, PE 14 UL: L1, L2, L3 + G 15

340-456

340-480

353-498

374-528

408-576

40-70

1001

950

914

853

791

1107

1063

1024

956

910

1113

1040

950

<3% at 100% load, <4% at 50% load, <9% at 25% load

0.99 at >40% load, 0.98 at >20% load, 0.97 at >10% load

Contactors Adaptive 1-300 seconds

IEC: L1, L2, L3, N, PE or L1, L2, L3, PE 18 UL: L1, L2, L3, G or L1, L2, L3, N, G

342-418

360-440

374-457

396-484

432-528

50 or 60

Programmable: ±0.1, ±3, ±10. Default is ±3

959

911

878

828

757

100 kA RMS (conditioned by an internal molded switch with 90 kA peak magnetic trip)

9680 (1250 kW I/O)

9165 (1250 kW I/O)

39 kA

Molded switch with trip for backfeed protection

IEC: L1, L2, L3, N, PE or L1, L2, L3, PE UL: L1, L2, L3, G, GEC19 or L1, L2, L3, N, G

Normal operation: 150% for 1 minute, 125% for 10 minutes Battery operation: 115% for 1 minute Bypass operation: 110%20 continuous, 1000% for 60 milliseconds for systems with 1250 kW I/O cabinet and 100 milliseconds for systems with 1500 kW I/O cabinet

Balanced load: ±1%, Unbalanced load: ±3%

±5% after 2 ms, ±1% after 50 ms

1

950

902

870

820

752

<2% at 100% linear load, <3% at 100% non-linear load

50/60 (synchronized to bypass), 50/60 Hz ±0.1% (free-running)

Programmable: 0.25, 0.5, 1, 2, 4, 6

Double-conversion: VFI-SS-111

Up to 3 (THDU < 5%) 0.7 leading to 0.5 lagging without derating

Output Specifications

14. TN, TT, and IT power distribution systems are supported. 15. WYE source ­ solid grounded and high resistance grounded sources are supported. Corner (line) grounding is not supported. 16. The system can operate at 600 V for 1 minute. 17. At nominal input voltage and full charge. 18. TN, TT, and IT power distribution systems with no earthed line conductors are supported. 19. Per NEC 250.30. 20. 125% for 480 V.

26

990-5451F-001

Facility Planning

Battery Specifications

Voltage (V) Charging power in % of output power

380

400

415

35% at  80% load, 12% at 100% load

440 V

Maximum charging power (kW)

75 at 100% load, 218.75 at <80% load

Nominal battery voltage (VDC) Nominal float voltage (VDC) End of discharge voltage (full load) (VDC) End of discharge voltage (no load) (VDC) Battery current at full load and nominal battery voltage (A) Battery current at full load and minimum battery voltage (A) Maximum battery backup time Temperature compensation (per cell) Ripple current Battery test Deep discharge protection Recharge according to battery temperature

480 546 384 420 1362
1703
Unlimited -3.3 mV per °C for T  25 °C, 0 mV per °C for T < 25 °C < 5% C20 (5 minutes backup time) Manual/automatic (selectable) Yes Yes

480 V UPS System
480 V 40% at  80% load, 15% at 100% load 93.75 at 100% load, 250 at 80% load

990-5451F-001

27

480 V UPS System
Specifications for 750 kW UPS

Facility Planning

Input Specifications

Bypass Specifications

Voltage (V) Connections
Input voltage range (V)23 Frequency (Hz) Nominal input current (A) Maximum input current (A)24 Input current limitation (A) Total harmonic distortion (THDI) Input power factor Protection Ramp-in Connections
Bypass voltage range (V) Frequency (Hz) Frequency range (Hz) Nominal bypass current (A) Maximum short circuit rating Thyristor I²t (kA*s²)
BF2 magnetic trip Protection Connections
Overload capacity
Output voltage tolerance Dynamic load response Output power factor Nominal output current (A) Total harmonic distortion (THDU) Output frequency (Hz) Slew rate (Hz/sec) Output performance classification (according to IEC/ EN62040-3) Load crest factor Load power factor

380

400

415

440 V

480 V

IEC: L1, L2, L3, PE 21 UL: L1, L2, L3 + G 22

340-456

340-480

353-498

374-528

408-576

40-70

1201

1139

1097

1029

950

1328

1276

1229

1153

1092

1335

1248

1140

<3% at 100% load, <4% at 50% load, <9% at 25% load

0.99 at >40% load, 0.98 at >20% load, 0.97 at >10% load

Contactors Adaptive 1-300 seconds

IEC: L1, L2, L3, N, PE or L1, L2, L3, PE 25 UL: L1, L2, L3, G or L1, L2, L3, N, G

342-418

360-440

374-457

396-484

432-528

50 or 60

Programmable: ±0.1, ±3, ±10. Default is ±3

1151

1093

1054

994

909

100 kA RMS (conditioned by an internal molded switch with 90 kA peak magnetic trip)

9680 (1250 kW I/O) 16245 (1500 kW I/O)

9165 (1250 kW I/O) 16245 (1500 kW I/O)

39 kA

Molded switch with trip for backfeed protection

IEC: L1, L2, L3, N, PE or L1, L2, L3, PE UL: L1, L2, L3, G, GEC26 or L1, L2, L3, N, G

Normal operation: 150% for 1 minute, 125% for 10 minutes Battery operation: 115% for 1 minute Bypass operation: 110%27 continuous, 1000% for 60 milliseconds for systems with 1250 kW I/O cabinet and 100 milliseconds for systems with 1500 kW I/O cabinet

Balanced load: ±1%, Unbalanced load: ±3%

±5% after 2 ms, ±1% after 50 ms

1

1140

1083

1043

984

902

<2% at 100% linear load, <3% at 100% non-linear load

50/60 (synchronized to bypass), 50/60 Hz ±0.1% (free-running)

Programmable: 0.25, 0.5, 1, 2, 4, 6

Double-conversion: VFI-SS-111

Up to 3 (THDU < 5%) 0.7 leading to 0.5 lagging without derating

Output Specifications

21. TN, TT, and IT power distribution systems are supported. 22. WYE source ­ solid grounded and high resistance grounded sources are supported. Corner (line) grounding is not supported. 23. The system can operate at 600 V for 1 minute. 24. At nominal input voltage and full charge. 25. TN, TT, and IT power distribution systems with no earthed line conductors are supported. 26. Per NEC 250.30. 27. 125% for 480 V.

28

990-5451F-001

Facility Planning

Battery Specifications

Voltage (V) Charging power in % of output power

380

400

415

35% at  80% load, 12% at 100% load

440 V

Maximum charging power (kW)

90 at 100% load, 262 at <80% load

Nominal battery voltage (VDC) Nominal float voltage (VDC) End of discharge voltage (full load) (VDC) End of discharge voltage (no load) (VDC) Battery current at full load and nominal battery voltage (A) Battery current at full load and minimum battery voltage (A) Maximum battery backup time Temperature compensation (per cell) Ripple current Battery test Deep discharge protection Recharge according to battery temperature

480 546 384 420 1634
2043
Unlimited -3.3 mV per °C for T  25 °C, 0 mV per °C for T < 25 °C < 5% C20 (5 minutes backup time) Manual/automatic (selectable) Yes Yes

480 V UPS System
480 V 40% at  80% load, 15% at 100% load 112.5 at 100% load, 300 at 80% load

990-5451F-001

29

480 V UPS System
Specifications for 800 kW UPS

Facility Planning

Input Specifications

Bypass Specifications

Voltage (V) Connections
Input voltage range (V)30 Frequency (Hz) Nominal input current (A) Maximum input current (A)31 Input current limitation (A) Total harmonic distortion (THDI) Input power factor Protection Ramp-in Connections
Bypass voltage range (V) Frequency (Hz) Frequency range (Hz) Nominal bypass current (A) Maximum short circuit rating Thyristor I²t (kA*s²) BF2 magnetic trip Protection Connections
Overload capacity
Output voltage tolerance Dynamic load response Output power factor Nominal output current (A) Total harmonic distortion (THDU) Output frequency (Hz) Slew rate (Hz/sec) Output performance classification (according to IEC/ EN62040-3) Load crest factor Load power factor

380

400

415

440 V

480 V

IEC: L1, L2, L3, PE 28 UL: L1, L2, L3 + G 29

340-456

340-480

353-498

374-528

408-576

40-70

1281

1215

1170

1098

1013

1417

1361

1311

1230

1165

1424

1331

1216

<3% at 100% load, <4% at 50% load, <9% at 25% load

0.99 at >40% load, 0.98 at >20% load, 0.97 at >10% load

Contactors Adaptive 1-300 seconds

IEC: L1, L2, L3, N, PE or L1, L2, L3, PE 32 UL: L1, L2, L3, G or L1, L2, L3, N, G

342-418

360-440

374-457

396-484

432-528

50 or 60

Programmable: ±0.1, ±3, ±10. Default is ±3

1228

1166

1124

1060

969

100 kA RMS (conditioned by an internal molded switch with 90 kA peak magnetic trip)

9680 (1250 kW I/O)

9165 (1250 kW I/O)

39 kA

Molded switch with trip for backfeed protection

IEC: L1, L2, L3, N, PE or L1, L2, L3, PE UL: L1, L2, L3, G, GEC33 or L1, L2, L3, N, G

Normal operation: 150% for 1 minute, 125% for 10 minutes Battery operation: 115% for 1 minute Bypass operation: 110%34 continuous, 1000% for 60 milliseconds for systems with 1250 kW I/O cabinet and 100 milliseconds for systems with 1500 kW I/O cabinet

Balanced load: ±1%, Unbalanced load: ±3%

±5% after 2 ms, ±1% after 50 ms

1

1216

1155

1113

1050

962

<2% at 100% linear load, <3% at 100% non-linear load

50/60 (synchronized to bypass), 50/60 Hz ±0.1% (free-running)

Programmable: 0.25, 0.5, 1, 2, 4, 6

Double-conversion: VFI-SS-111

Up to 3 (THDU < 5%) 0.7 leading to 0.5 lagging without derating

Output Specifications

28. TN, TT, and IT power distribution systems are supported. 29. WYE source ­ solid grounded and high resistance grounded sources are supported. Corner (line) grounding is not supported. 30. The system can operate at 600 V for 1 minute. 31. At nominal input voltage and full charge. 32. TN, TT, and IT power distribution systems with no earthed line conductors are supported. 33. Per NEC 250.30. 34. 125% for 480 V.

30

990-5451F-001

Facility Planning

Battery Specifications

Voltage (V) Charging power in % of output power

380

400

415

35% at  80% load, 12% at 100% load

440 V

Maximum charging power (kW)

96 at 100% load, 280 at <80% load

Nominal battery voltage (VDC) Nominal float voltage (VDC) End of discharge voltage (full load) (VDC) End of discharge voltage (no load) (VDC) Battery current at full load and nominal battery voltage (A) Battery current at full load and minimum battery voltage (A) Maximum battery backup time Temperature compensation (per cell) Ripple current Battery test Deep discharge protection Recharge according to battery temperature

480 546 384 420 1743
2179
Unlimited -3.3 mV per °C for T  25 °C, 0 mV per °C for T < 25 °C < 5% C20 (5 minutes backup time) Manual/automatic (selectable) Yes Yes

480 V UPS System
480 V 40% at  80% load, 15% at 100% load 120 at 100% load, 320 at 80% load

990-5451F-001

31

480 V UPS System
Specifications for 1000 kW UPS

Facility Planning

Input Specifications

Bypass Specifications

Voltage (V) Connections
Input voltage range (V)37 Frequency (Hz) Nominal input current (A) Maximum input current (A)38 Input current limitation (A) Total harmonic distortion (THDI) Input power factor Protection Ramp-in Connections
Bypass voltage range (V) Frequency (Hz) Frequency range (Hz) Nominal bypass current (A) Maximum short circuit rating Thyristor I²t (kA*s²)
BF2 magnetic trip Protection Connections
Overload capacity
Output voltage tolerance Dynamic load response Output power factor Nominal output current (A) Total harmonic distortion (THDU) Output frequency (Hz) Slew rate (Hz/sec) Output performance classification (according to IEC/ EN62040-3) Load crest factor Load power factor

380

400

415

440 V

480 V

IEC: L1, L2, L3, PE 35 UL: L1, L2, L3 + G 36

340-456

340-480

353-498

374-528

408-576

40-70

1601

1519

1463

1370

1266

1771

1702

1638

1534

1456

1780

1664

1520

<3% at 100% load, <4% at 50% load, <9% at 25% load

0.99 at >40% load, 0.98 at >20% load, 0.97 at >10% load

Contactors Adaptive 1-300 seconds

IEC: L1, L2, L3, N, PE or L1, L2, L3, PE 39 UL: L1, L2, L3, G or L1, L2, L3, N, G

342-418

360-440

374-457

396-484

432-528

50 or 60

Programmable: ±0.1, ±3, ±10. Default is ±3

1535

1458

1405

1325

1211

100 kA RMS (conditioned by an internal molded switch with 90 kA peak magnetic trip)

9680 (1250 kW I/O) 16245 (1500 kW I/O)

9165 (1250 kW I/O) 16245 (1500 kW I/O)

39 kA

Molded switch with trip for backfeed protection

IEC: L1, L2, L3, N, PE or L1, L2, L3, PE UL: L1, L2, L3, G, GEC40 or L1, L2, L3, N, G

Normal operation: 150% for 1 minute, 125% for 10 minutes Battery operation: 115% for 1 minute Bypass operation: 110%41 continuous, 1000% for 60 milliseconds for systems with 1250 kW I/O cabinet and 100 milliseconds for systems with 1500 kW I/O cabinet

Balanced load: ±1%, Unbalanced load: ±3%

±5% after 2 ms, ±1% after 50 ms

1

1519

1443

1391

1312

1203

<2% at 100% linear load, <3% at 100% non-linear load

50/60 (synchronized to bypass), 50/60 Hz ±0.1% (free-running)

Programmable: 0.25, 0.5, 1, 2, 4, 6

Double-conversion: VFI-SS-111

Up to 3 (THDU < 5%) 0.7 leading to 0.5 lagging without derating

Output Specifications

35. TN, TT, and IT power distribution systems are supported. 36. WYE source ­ solid grounded and high resistance grounded sources are supported. Corner (line) grounding is not supported. 37. The system can operate at 600 V for 1 minute. 38. At nominal input voltage and full charge. 39. TN, TT, and IT power distribution systems with no earthed line conductors are supported. 40. Per NEC 250.30. 41. 125% for 480 V.

32

990-5451F-001

Facility Planning

Battery Specifications

Voltage (V) Charging power in % of output power

380

400

415

35% at  80% load, 12% at 100% load

440 V

Maximum charging power (kW)

120 at 100% load, 350 at <80% load

Nominal battery voltage (VDC) Nominal float voltage (VDC) End of discharge voltage (full load) (VDC) End of discharge voltage (no load) (VDC) Battery current at full load and nominal battery voltage (A) Battery current at full load and minimum battery voltage (A) Maximum battery backup time Temperature compensation (per cell) Ripple current Battery test Deep discharge protection Recharge according to battery temperature

480 546 384 420 2179
2724
Unlimited -3.3 mV per °C for T  25 °C, 0 mV per °C for T < 25 °C < 5% C20 (5 minutes backup time) Manual/automatic (selectable) Yes Yes

480 V UPS System
480 V 40% at  80% load, 15% at 100% load 150 at 100% load, 400 at <80% load

990-5451F-001

33

480 V UPS System
Specifications for 1100 kW UPS

Facility Planning

Input Specifications

Bypass Specifications

Voltage (V) Connections
Input voltage range (V)44 Frequency (Hz) Nominal input current (A) Maximum input current (A)45 Input current limitation (A) Total harmonic distortion (THDI) Input power factor Protection Ramp-in Connections
Bypass voltage range (V) Frequency (Hz) Frequency range (Hz) Nominal bypass current (A) Maximum short circuit rating Thyristor I²t (kA*s²) BF2 magnetic trip Protection Connections
Overload capacity
Output voltage tolerance Dynamic load response Output power factor Nominal output current (A) Total harmonic distortion (THDU) Output frequency (Hz) Slew rate (Hz/sec) Output performance classification (according to IEC/ EN62040-3) Load crest factor Load power factor

380

400

415

440 V

480 V

IEC: L1, L2, L3, PE 42 UL: L1, L2, L3 + G 43

340-456

340-480

353-498

374-528

408-576

40-70

1761

1671

1609

1510

1393

1948

1872

1802

1691

1602

1958

1830

1672

<3% at 100% load, <4% at 50% load, <9% at 25% load

0.99 at >40% load, 0.98 at >20% load, 0.97 at >10% load

Contactors Adaptive 1-300 seconds

IEC: L1, L2, L3, N, PE or L1, L2, L3, PE 46 UL: L1, L2, L3, G or L1, L2, L3, N, G

342-418

360-440

374-457

396-484

432-528

50 or 60

Programmable: ±0.1, ±3, ±10. Default is ±3

1688

1604

1546

1458

1332

100 kA RMS (conditioned by an internal molded switch with 90 kA peak magnetic trip)

9680 (1250 kW I/O)

9165 (1250 kW I/O)

39 kA

Molded switch with trip for backfeed protection

IEC: L1, L2, L3, N, PE or L1, L2, L3, PE UL: L1, L2, L3, G, GEC47 or L1, L2, L3, N, G

Normal operation: 150% for 1 minute, 125% for 10 minutes Battery operation: 115% for 1 minute Bypass operation: 110%48 continuous, 1000% for 60 milliseconds for systems with 1250 kW I/O cabinet and 100 milliseconds for systems with 1500 kW I/O cabinet

Balanced load: ±1%, Unbalanced load: ±3%

±5% after 2 ms, ±1% after 50 ms

1

1671

1588

1530

1443

1323

<2% at 100% linear load, <3% at 100% non-linear load

50/60 (synchronized to bypass), 50/60 Hz ±0.1% (free-running)

Programmable: 0.25, 0.5, 1, 2, 4, 6

Double-conversion: VFI-SS-111

Up to 3 (THDU < 5%) 0.7 leading to 0.5 lagging without derating

Output Specifications

42. TN, TT, and IT power distribution systems are supported. 43. WYE source ­ solid grounded and high resistance grounded sources are supported. Corner (line) grounding is not supported. 44. The system can operate at 600 V for 1 minute. 45. At nominal input voltage and full charge. 46. TN, TT, and IT power distribution systems with no earthed line conductors are supported. 47. Per NEC 250.30. 48. 125% for 480 V.

34

990-5451F-001

Facility Planning

Battery Specifications

Voltage (V) Charging power in % of output power

380

400

415

35% at  80% load, 12% at 100% load

440 V

Maximum charging power (kW)

132 at 100% load, 385 at <80% load

Nominal battery voltage (VDC) Nominal float voltage (VDC) End of discharge voltage (full load) (VDC) End of discharge voltage (no load) (VDC) Battery current at full load and nominal battery voltage (A) Battery current at full load and minimum battery voltage (A) Maximum battery backup time Temperature compensation (per cell) Ripple current Battery test Deep discharge protection Recharge according to battery temperature

480 546 384 420 2397
2996
Unlimited -3.3 mV per °C for T  25 °C, 0 mV per °C for T < 25 °C < 5% C20 (5 minutes backup time) Manual/automatic (selectable) Yes Yes

480 V UPS System
480 V 40% at  80% load, 15% at 100% load 165 at 100% load, 440 at <80% load

990-5451F-001

35

480 V UPS System
Specifications for 1250 kW UPS

Facility Planning

Input Specifications

Bypass Specifications

Voltage (V) Connections
Input voltage range (V)51 Frequency (Hz) Nominal input current (A) Maximum input current (A)52 Input current limitation (A) Total harmonic distortion (THDI) Input power factor Protection Ramp-in Connections
Bypass voltage range (V) Frequency (Hz) Frequency range (Hz) Nominal bypass current (A) Maximum short circuit rating Thyristor I²t (kA*s²)
BF2 magnetic trip Protection Connections
Overload capacity
Output voltage tolerance Dynamic load response Output power factor Nominal output current (A) Total harmonic distortion (THDU) Output frequency (Hz) Slew rate (Hz/sec) Output performance classification (according to IEC/ EN62040-3) Load crest factor Load power factor

380

400

415

440 V

480 V

IEC: L1, L2, L3, PE 49 UL: L1, L2, L3 + G 50

340-456

340-480

353-498

374-528

408-576

40-70

2001

1899

1828

1716

1583

2214

2127

2048

1922

1820

2225

2080

1900

<3% at 100% load, <4% at 50% load, <9% at 25% load

0.99 at >40% load, 0.98 at >20% load, 0.97 at >10% load

Contactors Adaptive 1-300 seconds

IEC: L1, L2, L3, N, PE or L1, L2, L3, PE 53 UL: L1, L2, L3, G or L1, L2, L3, N, G

342-418

360-440

374-457

396-484

432-528

50 or 60

Programmable: ±0.1, ±3, ±10. Default is ±3

1918

1822

1757

1657

1514

100 kA RMS (conditioned by an internal molded switch with 90 kA peak magnetic trip)

9680 (1250 kW I/O) 16245 (1500 kW I/O)

9165 (1250 kW I/O) 16245 (1500 kW I/O)

39 kA

Molded switch with trip for backfeed protection

IEC: L1, L2, L3, N, PE or L1, L2, L3, PE UL: L1, L2, L3, G, GEC54 or L1, L2, L3, N, G

Normal operation: 150% for 1 minute, 125% for 10 minutes Battery operation: 115% for 1 minute Bypass operation: 110%55 continuous, 1000% for 60 milliseconds for systems with 1250 kW I/O cabinet and 100 milliseconds for systems with 1500 kW I/O cabinet

Balanced load: ±1%, Unbalanced load: ±3%

±5% after 2 ms, ±1% after 50 ms

1

1899

1804

1739

1640

1504

<2% at 100% linear load, <3% at 100% non-linear load

50/60 (synchronized to bypass), 50/60 Hz ±0.1% (free-running)

Programmable: 0.25, 0.5, 1, 2, 4, 6

Double-conversion: VFI-SS-111

Up to 3 (THDU < 5%) 0.7 leading to 0.5 lagging without derating

Output Specifications

49. TN, TT, and IT power distribution systems are supported. 50. WYE source ­ solid grounded and high resistance grounded sources are supported. Corner (line) grounding is not supported. 51. The system can operate at 600 V for 1 minute. 52. At nominal input voltage and full charge. 53. TN, TT, and IT power distribution systems with no earthed line conductors are supported. 54. Per NEC 250.30. 55. 125% for 480 V.

36

990-5451F-001

Facility Planning

Battery Specifications

Voltage (V) Charging power in % of output power

380

400

415

35% at  80% load, 12% at 100% load

440 V

Maximum charging power (kW)

150 at 100% load, 437 at <80% load

Nominal battery voltage (VDC) Nominal float voltage (VDC) End of discharge voltage (full load) (VDC) End of discharge voltage (no load) (VDC) Battery current at full load and nominal battery voltage (A) Battery current at full load and minimum battery voltage (A) Maximum battery backup time Temperature compensation (per cell) Ripple current Battery test Deep discharge protection Recharge according to battery temperature

480 546 384 420 2724
3405
1 hour -3.3 mV per °C for T  25 °C, 0 mV per °C for T < 25 °C < 5% C20 (5 minutes backup time) Manual/automatic (selectable) Yes Yes

480 V UPS System
480 V 40% at  80% load, 15% at 100% load 187.5 at 100% load, 500 at <80% load

990-5451F-001

37

480 V UPS System
Specifications for 1500 kW UPS

Facility Planning

Input Specifications

Bypass Specifications

Voltage (V) Connections
Input voltage range (V)58 Frequency (Hz) Nominal input current (A) Maximum input current (A)59 Input current limitation (A) Total harmonic distortion (THDI) Input power factor Protection Ramp-in Connections
Bypass voltage range (V) Frequency (Hz) Frequency range (Hz) Nominal bypass current (A) Maximum short circuit rating Thyristor I²t (kA*s²) BF2 magnetic trip Protection Connections
Overload capacity
Output voltage tolerance Dynamic load response Output power factor Nominal output current (A) Total harmonic distortion (THDU) Output frequency (Hz) Slew rate (Hz/sec) Output performance classification (according to IEC/ EN62040-3) Load crest factor Load power factor

380

400

415

440 V

480 V

IEC: L1, L2, L3, PE 56 UL: L1, L2, L3 + G 57

340-456

340-480

353-498

374-528

408-576

40-70

2401

2279

2194

2059

1899

2657

2552

2457

2306

2184

2670

2496

2280

<3% at 100% load, <4% at 50% load, <9% at 25% load

0.99 at >40% load, 0.98 at >20% load, 0.97 at >10% load

Contactors Adaptive 1-300 seconds

IEC: L1, L2, L3, N, PE or L1, L2, L3, PE 60 UL: L1, L2, L3, G or L1, L2, L3, N, G

342-418

360-440

374-457

396-484

432-528

50 or 60

Programmable: ±0.1, ±3, ±10. Default is ±3

2302

2187

2108

1988

1817

100 kA RMS (conditioned by an internal molded switch with 90 kA peak magnetic trip)

16245 (1500 kW I/O)

39 kA

Molded switch with trip for backfeed protection

IEC: L1, L2, L3, N, PE or L1, L2, L3, PE UL: L1, L2, L3, G, GEC61 or L1, L2, L3, N, G

150% for 1 minute, 125% for 10 minutes (normal operation) 115% for 1 minute (battery operation) 110% continuous,1000% for 100 milliseconds (bypass operation)

Balanced load: ±1%, Unbalanced load: ±3%

±5% after 2 ms, ±1% after 50 ms

1

2279

2165

2087

1968

1804

<2% at 100% linear load, <3% at 100% non-linear load

50/60 (synchronized to bypass), 50/60 Hz ±0.1% (free-running)

Programmable: 0.25, 0.5, 1, 2, 4, 6

Double-conversion: VFI-SS-111

Up to 3 (THDU < 5%) 0.7 leading to 0.5 lagging without derating

Output Specifications

56. TN, TT, and IT power distribution systems are supported. 57. WYE source ­ solid grounded and high resistance grounded sources are supported. Corner (line) grounding is not supported. 58. The system can operate at 600 V for 1 minute. 59. At nominal input voltage and full charge. 60. TN, TT, and IT power distribution systems with no earthed line conductors are supported. 61. Per NEC 250.30.

38

990-5451F-001

Facility Planning

Battery Specifications

Voltage (V) Charging power in % of output power

380

400

415

35% at  80% load, 12% at 100% load

440 V

Maximum charging power (kW)

525 at < 80% load, 180 at 100% load,

Nominal battery voltage (VDC) Nominal float voltage (VDC) End of discharge voltage (full load) (VDC) End of discharge voltage (no load) (VDC) Battery current at full load and nominal battery voltage (A) Battery current at full load and minimum battery voltage (A) Maximum battery backup time Temperature compensation (per cell) Ripple current Battery test Deep discharge protection Recharge according to battery temperature

480 546 384 420 3269
4086
1 hour -3.3 mV per °C for T  25 °C, 0 mV per °C for T < 25 °C < 5% C20 (5 minutes backup time) Manual/automatic (selectable) Yes Yes

480 V UPS System
480 V 40% at  80% load, 15% at 100% load 600 at <80% load, 225 at 100% load

Recommended Upstream Protection and Cable Sizes ­ UL
CAUTION
HAZARD OF FIRE · Connect only to a circuit with the below specifications. · Connect only to a circuit provided with maximum a 1600 A branch circuit
overcurrent protection in accordance with the National Electrical Code, ANSI/NFPA70, and the Canadian Electrical Code, Part I, C22.1. Failure to follow these instructions can result in injury or equipment damage.
NOTE: Overcurrent protection is to be provided by others. NOTE: All wiring must comply with all applicable national and/or electrical code (National Electrical Code, ANSI/NFPA 70). Cable sizes in this manual are based on Table 310.15 of the National Electrical Code 2014 (NEC) with the following assertions: · 90 °C conductors (THHN) for 75 °C termination · Not more than 3 current carrying conductors in each conduit · An ambient temperature of max. 30 °C · Use of copper or aluminium conductors · 100% rated breakers · Nominal operating conditions If the ambient room temperature is greater than 30 °C, use larger or additional parallel conductors in accordance with the correction factors of the NEC. The maximum allowable conductor size is 600 kcmil.
Equipment Grounding Conductors (EGC) are sized in accordance with NEC Article 250.122 and Table 250.122 Minimum size equipment conductor for grounding equipment.

990-5451F-001

39

480 V UPS System

Facility Planning

NOTE: Always consider the EGC size according to the complete electrical installation.
NOTE: The use of aluminium conductors can limit the number of parallel Li-ion battery cabinets. Please contact Schneider Electric for more information.

Recommended Upstream Protection and Cable Sizes for 500 kW UPS

Maximum OCPD (A)

Input Bypass Output Battery

800 (Ir = 1.0) 700 (Ir = 1.0) 700 (Ir = 1.0) 1600 (Ir = 0.9)

Conductors per Phase Copper / Aluminium (kcmil) 2x500 / 3x400 2x350 / 2x500 2x350 / 2x500 4x500 / 5x500

Equipment Grounding Conductor Copper / Aluminium62 1/0 AWG / 3/0 AWG 1/0 AWG / 3/0 AWG 1/0 AWG / 3/0 AWG 4/0 AWG / 350 kcmil

Recommended Upstream Protection and Cable Sizes for 625 kW UPS

Maximum OCPD (A)

Input Bypass Output Battery

1000 (Ir = 1.0) 800 (Ir= 1.0) 800 (Ir = 1.0) 2000 (Ir = 0.9)

Conductors per Phase Copper/ Aluminium (kcmil) 3x400 / 3x600 2x600 / 3x400 2x600 / 3x400 5x500 / 6x500

Equipment Grounding Conductor Copper/Aluminium62 2/0 AWG / 4/0 AWG 1/0 AWG / 3/0 AWG 1/0 AWG / 3/0 AWG 250 kcmil / 400 kcmil

Recommended Upstream Protection and Cable Sizes for 750 kW UPS

Maximum OCPD (A)

Input Bypass Output Battery

1200 (Ir = 1.0) 1000 (Ir = 1.0) 1000 (Ir = 1.0) 2500 (Ir = 0.9)

Conductors per Phase Copper/ Aluminium (kcmil) 3x600 / 4x500 3x400 / 3x600 3x400 / 3x600 6x500 / 7x600

Equipment Grounding Conductor Copper/Aluminium62 3/0 AWG / 250 kcmil 2/0 AWG / 4/0 AWG 2/0 AWG / 4/0 AWG 350 kcmil / 600 kcmil

Recommended Upstream Protection and Cable Sizes for 800 kW UPS

Maximum OCPD (A)

Input Bypass Output Battery

1600 (Ir = 0.8) 1000 1000 2500 (Ir = 0.9)

Conductors per Phase Copper/ Aluminium (kcmil) 4x400 / 4x600 3x400 / 3x600 3x400 / 3x600 6x500 / 7x600

Equipment Grounding Conductor Copper/Aluminium62 4/0 AWG / 350 kcmil 2/0 AWG / 4/0 AWG 2/0 AWG / 4/0 AWG 350 kcmil / 600 kcmil

62. If the conductors are run in conduits, there must be one conductor in each conduit. 40

990-5451F-001

Facility Planning

480 V UPS System

Recommended Upstream Protection and Cable Sizes for 1000 kW UPS

Maximum OCPD (A)

Input Bypass Output Battery

1600 (Ir = 1.0) 1600 (Ir = 0.8) 1600 (Ir = 0.8) 3000 (Ir = 1.0)

Conductors per Phase Copper/ Aluminium (kcmil) 4x600 / 5x600 4x400 / 4x600 4x400 / 4x600 8x500 / 9x600

Equipment Grounding Conductor Copper/Aluminium63 4/0 AWG / 350 kcmil 4/0 AWG / 350 kcmil 4/0 AWG / 350 kcmil 400 kcmil / 600 kcmil

Recommended Upstream Protection and Cable Sizes for 1100 kW UPS

Maximum OCPD (A)

Input Bypass Output Battery

2000 (Ir = 0.9) 1600 (Ir = 0.9) 1600 (Ir = 0.9) 3000 (Ir = 1.0)

Conductors per Phase Copper/ Aluminium (kcmil) 5x500 / 6x500 4x500 / 5x500 4x500 / 5x500 8x500 / 9x600

Equipment Grounding Conductor Copper/Aluminium63 250 kcmil/ 400 kcmil 4/0 AWG / 350 kcmil 4/0 AWG / 350 kcmil 400 kcmil / 600 kcmil

Recommended Upstream Protection and Cable Sizes for 1250 kW UPS

Maximum OCPD (A)

Input Bypass Output Battery

2000 (Ir = 1.0) 1600 (Ir = 1.0) 1600 (Ir = 1.0) 4000 (Ir = 0.9)

Conductors per Phase Copper/ Aluminium (kcmil) 5x600 / 6x600 4x600 / 5x600 4x600 / 5x600 9x600 / 11x600

Equipment Grounding Conductor Copper/Aluminium63 250 kcmil / 400 kcmil 4/0 AWG / 350 kcmil 4/0 AWG / 350 kcmil 500 kcmil / 750 kcmil

Recommended Upstream Protection and Cable Sizes for 1500 kW UPS

Maximum OCPD (A)

Input

250064

Bypass 200064

Output 200064

Battery 500065

Conductors per Phase Copper/ Aluminium (kcmil)
6x600/ 8x600
5x600/ 6x600
5x600/ 6x600
11x600/ 14x600

Equipment Grounding Conductor Copper/Aluminium63
350 kcmil/ 400 kcmil
250 kcmil/ 350 kcmil
250 kcmil/ 350
700 kcmil/ ­

Recommended Bolt and Lug Sizes for Copper Cables

Cable Size 1/0 AWG 2/0 AWG 3/0 AWG

Terminal Bolt Diameter M12 x 35 mm M12 x 35 mm M12 x 35 mm

Cable Lug Type LCCF1/0­12­X LCCF2/0­12­X LCCF3/0­12­X

Crimping Tool CT930 CT930 CT930

Die CD-920­2/0 Black P45 CD-920­3/0 Orange P50 CD-920­4/0 Purple P54

63. If the conductors are run in conduits, there must be one conductor in each conduit. 64. Long-time setting (Ir) = 1.0 65. Long-time setting (Ir) = 0.9

990-5451F-001

41

480 V UPS System
Cable Size 250 kcmil 300 kcmil 400 kcmil 500 kcmil 600 kcmil

Terminal Bolt Diameter M12 x 35 mm M12 x 35 mm M12 x 35 mm M12 x 35 mm M12 x 40 mm

Cable Lug Type LCCF250­12­X LCCF300­12­6 LCCF400­12­6 LCCF500­12­6 LCCF600­12­6

Crimping Tool CT-940CH/CT-2940 CT-940CH/CT-2940 CT-940CH/CT-2940 CT-940CH/CT-2940 CT-940CH/CT-2940

Facility Planning
Die CD-920­300 White P66 CD-920­350 Red P71 CD-920­500 Brown P87 CD-920­500A Pink P99 CD-920­750 Black P106

Recommended Bolt and Lug Sizes for Aluminium Cables

Cable Size 2/0 AWG 3/0 AWG 250 kcmil 300 kcmil 400 kcmil 500 kcmil 600 kcmil

Terminal Bolt Diameter M12 x 40 mm M12 x 40 mm M12 x 40 mm M12 x 40 mm M12 x 40 mm M12 x 40 mm M12 x 40 mm

Cable Lug Type LAB2/0-12-5 LAB3/0-12-5 LAB250-12-5 LAB300-12-2 LAB400-12-2 LAB500-12-2 LAB600-12-2

Crimping Tool CT930 CT930 CT930 CT930 CT930 CT930 CT930

Die Olive P54 Ruby P60 Red P71 Blue P76 Green P94 Pink P99 Black P106

Weights and Dimensions

Weights and Dimensions for UPSs with 1250 kW I/O Cabinet

Commercial Reference
· GVX500K500NGS · GVX500K750NGS · GVX500K1000NGS · GVX500K1250NGS
· GVX625K625NGS · GVX625K1000NGS · GVX750K500NGS · GVX750K750NGS · GVX750K1000NGS · GVX750K1250NGS
· GVX800K800NGS · GVX1000K750NGS · GVX1000K1000NGS · GVX1000K1250NGS
· GVX1100K1100NGS · GVX1250K1000NGS · GVX1250K1250NGS
· GVX1500K1100NGS · GVX1500K1250NGS

Parts
Total ­ Power cabinets ­ I/O cabinet

Weight kg (lbs)
2030 (4475) 2x540 (2x1190) 950 (2094)

Total ­ Power cabinets ­ I/O cabinet

2570 (5666) 3x540 (3x1190) 950 (2094)

Total ­ Power cabinets ­ I/O cabinet

3110 (6856) 4x540 (4x1190) 950 (2094)

Total ­ Power cabinets ­ I/O cabinet

3650 (8047) 5x540 (5x1190) 950 (2094)

Total ­ Power cabinets ­ I/O cabinet

4190 (9237) 6x540 (6x1190) 950 (2094)

Height mm (in) 1970 (77.6) 1970 (77.6)
1970 (77.6) 1970 (77.6) 1970 (77.6)

Width mm (in) 2400 (94.5) 2x600 (2x23.6) 1200 (47.2)
3000 (118.1) 3x600 (3x23.6) 1200 (47.2)
3600 (141.7) 4x600 (4x23.6) 1200 (47.2)
4200 (165.4) 5x600 (5x23.6) 1200 (47.2)
4800 (189.0) 6x600 (6x23.6) 1200 (47.2)

Depth mm (in) 900 (35.4) 900 (35.4)
900 (35.4) 900 (35.4) 900 (35.4)

42

990-5451F-001

Facility Planning

480 V UPS System

Weights and Dimensions for UPSs with 1500 kW I/O Cabinet

Part Number · GVX500K1500GS · GVX750K1500GS · GVX1000K1500GS · GVX1250K1500GS · GVX1500K1500GS · GVX1750K1500GS

Parts
In total ­ Power cabinets ­ I/O cabinet
In total ­ Power cabinets ­ I/O cabinet
In total ­ Power cabinets ­ I/O cabinet
In total ­ Power cabinets ­ I/O cabinet
In total ­ Power cabinets ­ I/O cabinet
In total ­ Power cabinets ­ I/O cabinet

Weight kg (lbs)
1956 (4312) 2x540 (2x1190) 876 (1931)
2496 (5503) 3x540 (3x1190) 876 (1931)
3036 (6693) 4x540 (4x1190) 876 (1931)
3576 (7884) 5x540 (5x1190) 876 (1931)
4116 (9074) 6x540 (6x1190) 876 (1931)
4656 (10265) 7x540 (7x1190) 876 (1931)

Height mm (in) 1970 (77.6) 1970 (77.6) 1970 (77.6) 1970 (77.6) 1970 (77.6) 1970 (77.6)

Width mm (in)
3200 (126.0) 2x600 (2x23.6) 2000 (78.7)
3800 (149.6) 3x600 (3x23.6) 2000 (78.7)
4400 (173.2) 4x600 (4x23.6) 2000 (78.7)
5000 (196.9) 5x600 (5x23.6) 2000 (78.7)
5600 (220.5) 6x600 (6x23.6) 2000 (78.7)
6200 (244.1) 7x600 (7x23.6) 2000 (78.7)

Depth mm (in) 900 (35.4) 900 (35.4) 900 (35.4) 900 (35.4) 900 (35.4) 900 (35.4)

Maintenance Bypass Cabinet Weights and Dimensions

Part Number GVXMBCR625KG GVXMBCR750KG

Weight kg (lbs) 280 (617) 280 (617)

Height mm (in) 1970 (77.6) 1970 (77.6)

Width mm (in) 800 (31.5) 800 (31.5)

Depth mm (in) 900 (35.4) 900 (35.4)

Clearance
Clearance for UPSs with 1250 kW I/O Cabinet
NOTE: Clearance dimensions are published for airflow and service access only. Consult with the local safety codes and standards for additional requirements in your local area. NOTE: The UPS system can be placed up against a wall and there is no requirement for rear or side access.

990-5451F-001

43

480 V UPS System

Facility Planning

Clearance for UPSs with 1500 kW I/O Cabinet
NOTE: Clearance dimensions are published for airflow and service access only. Consult with the local safety codes and standards for additional requirements in your local area.
NOTE: The UPS system can be placed up against a wall with no requirement for rear or side access.

Front View

Guidance for Organizing Battery Cables
NOTE: For 3rd party batteries, use only high rate batteries for UPS applications. NOTE: When the battery bank is placed remotely, the organizing of the cables is important to reduce voltage drop and inductance. The distance between the battery bank and the UPS must not exceed 200 m (656 ft). Contact Schneider Electric for installations with a longer distance. NOTE: To minimize the risk of electromagnetic radiation, it is highly recommended to follow the below guidance and to use grounded metallic tray supports.
Cable Length

<30 m 31­75 m 76­150 m 151­200 m

Not recommended Not recommended Not recommended Not recommended

Acceptable Not recommended Not recommended Not recommended

Recommended Acceptable Acceptable Not recommended

Recommended Recommended Recommended Recommended

44

990-5451F-001

Facility Planning
Environment
Temperature

Operating
0 °C to 40 °C (32 °F to 104 °F)
0 °C to 50 °C (32 °F to 122 °F) when derated to 75% power66

Relative humidity

0 ­ 95% non-condensing

Altitude derating according to ANSI C57.96­ 1999

1000 m (3300 ft): 1.000 1500 m (5000 ft): 0.975 2000 m (6600 ft): 0.950 2500 m (8300 ft): 0.925 3000 m (10000 ft): 0.900

Audible noise one meter (three feet) from surface
Protection class Color

62 dB at 70% load 68 dB at 100% load IP20 RAL 9003 white

480 V UPS System
Storage -15 °C to 40 °C (5 °F to 104 °F) for systems with batteries -25 °C to 55 °C (-13 °F to 131 °F) for systems without batteries 0 ­ 95% non-condensing 0 ­ 15000 m (0 ­ 50000 ft)

Heat Dissipation (BTU/hr) for UPSs with 1250 kW I/O Cabinet

Heat Dissipation for 500 kW UPS

Normal operation

Voltage (V) 380

400

25% load 50% load 75% load 100% load

17771 34617 56095 78519

21504 38327 58889 80387

415 21504 38327 58889 78519

440 V 21504 37397 56095 75723

480 V 22920 36468 53313 72936

ECO mode

380

400

11385 8616 12924 13758

16847 11235 15540 17232

415 16387 10360 15540 17232

440 V 14099 12112 15540 17232

480 V 11835 13870 15540 17232

ECOnversion

Voltage (V) 380

400

25% load 50% load 75% load 100% load

4308 13870 12924 17232

7376 12990 14231 13758

415 6935 16521 14231 13758

440 V 10264 16078 15540 16362

480 V 13644 15635 16853 18975

Battery operation

380

400

14555 29110 75903 71083

15469 29110 47782 74793

415 15011 30938 49160 80387

440 V 15011 30938 49160 80387

480 V 15011 29110 49160 72936

Heat Dissipation for 625 kW UPS

Normal operation

Voltage (V) 380

400

25% load 50% load 75% load 100% load

27469 47909 73611 114602

26880 47909 73611 100484

415 26880 47909 73611 98149

440 V 26880 45006 67509 91170

480 V 28059 42118 61451 84236

ECO mode

380

400

10880 11859 16155 23718

13110 14044 19426 25901

415 13670 15139 19426 25901

440 V 13670 15139 19426 23718

480 V 13670 15139 19426 21540

66. For temperatures between 40 °C and 50 °C , derate the load power rating with 2.5% per °C

990-5451F-001

45

480 V UPS System

Facility Planning

ECOnversion

Voltage (V) 380

400

25% load 15922

15922

50% load 75% load

17337 21066

17337 21066

100% load 25901

25901

415 10880 17337 21066 25901

440 V 13390 17337 21066 24809

480 V 15922 17337 21066 23718

Battery operation

380

400

17056 40967 61451 86543

17056 39818 61451 84236

415 18764 38672 61451 100484

440 V 18764 38672 61451 100484

480 V 18764 36387 61451 91170

Heat Dissipation for 750 kW UPS

Normal operation

Voltage (V) 380

400

25% load 50% load 75% load 100% load

28745 56095 94653 146074

30847 56095 92542 137523

415 30847 54702 86236 129025

440 V 30847 53313 83097 120581

480 V 30847 51926 79969 112190

ECO mode

380

400

10402 14231 19386 25848

13056 16853 23311 28462

415 13723 18167 23311 28462

440 V 13723 18167 23311 28462

480 V 13723 18167 23311 28462

ECOnversion

Voltage (V) 380

400

25% load 15061

15061

50% load 19485

19485

75% load 25279

25279

100% load 31081

31081

415 9084 19485 25279 31081

440 V 12058 19485 25279 29771

480 V 15061 19485 25279 28462

Battery operation

380

400

21832

21832

45034

43664

77888

75812

114981 112190

415 22517 45034 75812 112190

440 V 22517 45034 75812 112190

480 V 23203 45034 75812 112190

Heat Dissipation for 800 kW UPS

Normal operation

Voltage (V) 380

400

25% load 50% load 75% load 100% load

35160 59835 91985 131616

35160 58349 89752 128620

415 34407 56867 85300 119669

440 V 34407 55387 84190 112253

480 V 34407 53911 83081 104876

ECO mode

380

400

15351 19378 22770 30360

15351 19378 22770 27572

415 8988 15180 22770 27572

440 V 8988 15180 22770 27572

480 V 8988 15180 22770 27572

ECOnversion

Voltage (V) 380

400

25% load 50% load 75% load 100% load

17497 20784 24865 30360

18216 20784 24865 30360

415 17497 20784 24865 27572

440 V 17857 20784 24865 26180

480 V 18216 20784 24865 24790

Battery operation

380

400

26956 50968 78657 113733

21831 43662 65493 101935

415 21105 48036 67676 104876

440 V 21105 48036 67676 104876

480 V 7590 48036 67676 104876

Heat Dissipation for 1000 kW UPS

Normal operation

Voltage (V) 380

400

25% load 36468

39259

50% load 75% load 100% load

71083 120581 187156

71083 117778 175802

415 39259 69234 109405 164520

440 V 39259 69234 109405 164520

480 V 39259 65547 101083 142167

ECO mode

380

400

12112

15635

15493

18975

20637

25848

27516

30987

415 16521 20721 25848 30987

440 V 16521 20721 25848 30987

480 V 16521 20721 25848 30987

46

990-5451F-001

Facility Planning

480 V UPS System

ECOnversion

Voltage (V) 380

400

25% load 18297

18297

50% load 75% load

22470 28462

22470 28462

100% load 34465

34465

415 10360 22470 28462 34465

440 V 14311 22470 28462 32725

480 V 18297 22470 28462 30987

Battery operation

380

400

28198 58219 101083 149587

28198 56397 98321 145873

415 29110 58219 98321 145873

440 V 29110 58219 98321 145873

480 V 30023 58219 98321 145873

Heat Dissipation for 1100 kW UPS

Normal operation

Voltage (V) 380

400

25% load 50% load 75% load 100% load

43185 82273 132639 201700

43185 78192 123409 185100

415 42160 76158 120345 180972

440 V 43185 76158 120345 180972

480 V 41136 70080 108153 152315

ECO mode

380

400

18173 22793 28433 37911

17199 22793 25564 37911

415 17199 22793 25564 37911

440 V 16713 21832 26998 35997

480 V 16227 20872 28433 34086

ECOnversion

Voltage (V) 380

400

25% load 21107

21107

50% load 24717

22793

75% load 34189

34189

100% load 53291

41744

415 20127 24717 34189 41744

440 V 18173 22793 28433 34086

480 V 21107 24717 31308 37911

Battery operation

380

400

35040

37064

66050

66050

163830 102095

156383 164545

415 36051 70080 105121 176852

440 V 32021 64041 108153 160460

480 V 36051 68063 105121 152315

Heat Dissipation for 1250 kW UPS

Normal operation

Voltage (V) 380

400

25% load 50% load 75% load 100% load

49074 93492 154237 233945

49074 88854 143726 215042

415 47909 86543 140237 210341

440 V 47909 83084 133281 193965

480 V 46746 79637 126354 177708

ECO mode

380

400

20651 25901 35578 43081

19544 25901 32311 43081

415 19544 25901 32311 43081

440 V 18992 24809 30680 40906

480 V 18440 23718 29050 38734

ECOnversion

Voltage (V) 380

400

25% load 50% load 75% load 100% load

22872 28088 35578 56175

22872 25901 35578 43081

415 21760 28088 35578 43081

440 V 22316 28088 33943 40906

480 V 22872 28088 32311 38734

Battery operation

380

400

36387 72774 119455 177708

38672 72774 119455 186983

415 37528 77345 122901 200969

440 V 37528 77345 122901 200969

480 V 37528 75057 122901 173085

990-5451F-001

47

480 V UPS System

Facility Planning

Heat Dissipation (BTU/hr) for UPSs with 1500 kW I/O Cabinet

Heat Dissipation for 500 kW UPS

Normal operation

Voltage (V) 380

400

25% load 50% load 75% load 100% load

17309 32774 53313 86017

16387 30938 50542 82260

415 16387 30938 50542 82260

440 V 16387 31396 50542 75723

480 V 18698 31855 50542 69234

ECO mode

380

400

5618 7747 11620 13758

5618 7747 11620 13758

415 5618 7747 11620 13758

440 V 6056 7747 10969 13758

480 V 6495 7747 10319 13758

ECOnversion

Voltage (V) 380

400

25% load 50% load 75% load 100% load

6495 7747 11620 15493

6495 7747 11620 13758

415 6495 7747 11620 13758

440 V 7155 7747 10969 13758

480 V 7818 7747 10319 13758

Battery operation

380

400

18234 31855 53313 78519

18234 31855 53313 78519

415 18234 31855 53313 78519

440 V 18234 31855 53313 78519

480 V 18234 31855 53313 78519

Heat Dissipation for 750 kW UPS

Normal operation

Voltage (V) 380

400

25% load 50% load 75% load 100% load

26656 51926 86236 134684

25271 49160 82053 129025

415 25271 49160 82053 129025

440 V 25271 47782 77888 117778

480 V 27351 46407 73741 106625

ECO mode

380

400

9084 12924 17430 23240

9084 12924 17430 23240

415 9084 12924 17430 23240

440 V 9413 12272 16453 21938

480 V 9742 11620 15478 20637

ECOnversion

Voltage (V) 380

400

25% load 50% load 75% load 100% load

9742 12924 17430 23240

9742 12924 17430 23240

415 9742 12924 17430 23240

440 V 10733 12924 16453 21938

480 V 11727 12924 15478 20637

Battery operation

380

400

27351 47782 79969 117778

27351 47782 79969 117778

415 27351 47782 79969 117778

440 V 27351 47782 79969 117778

480 V 27351 47782 79969 117778

Heat Dissipation for 1000 kW UPS

Normal operation

Voltage (V) 380

400

25% load 50% load 75% load 100% load

36468 71083 123390 187156

34617 67389 117778 179579

415 34617 67389 117778 179579

440 V 33888 60137 98514 149141

480 V 36468 61876 95564 145873

ECO mode

380

400

12112 17232 23240 30987

12112 17232 23240 30987

415 12112 17232 23240 30987

440 V 12112 16362 21938 29251

480 V 12112 15493 20637 27516

48

990-5451F-001

Facility Planning

480 V UPS System

ECOnversion

Voltage (V) 380

400

25% load 13334

13334

50% load 75% load

17254 24358

17254 24358

100% load 31342

31342

415 13334 17254 24358 31342

440 V 14313 16956 22496 29428

480 V 15294 16657 20637 27516

Battery operation

380

400

36468 63710 106625 157038

35819 62976 104128 156664

415 36468 63710 106625 157038

440 V 36468 63710 106625 157038

480 V 36468 63710 106625 157038

Heat Dissipation for 1250 kW UPS

Normal operation

Voltage (V) 380

400

25% load 50% load 75% load 100% load

44427 86543 147223 224474

42118 81934 140237 215042

415 42118 81934 140237 215042

440 V 42118 78490 129814 196297

480 V 44427 75057 119455 177708

ECO mode

380

400

12950 19367 25796 30065

12950 19367 25796 30065

415 12950 19367 25796 30065

440 V 13497 18282 24172 30065

480 V 14044 17198 22549 30065

ECOnversion

Voltage (V) 380

400

25% load 15569

15569

50% load 19394

19394

75% load 27191

27191

100% load 34838

34838

415 15569 19394 27191 34838

440 V 17156 19721 25681 32451

480 V 18748 20047 24172 30065

Battery operation

380

400

45585

45585

79637

79637

133281 133281

196297 196297

415 45585 79637 133281 196297

440 V 45585 79637 133281 196297

480 V 45585 79637 133281 196297

Heat Dissipation for 1500 kW UPS

Normal operation

Voltage 380

400

(V)

25% load 53313 50% load 103851

50542 98321

75% load
100% load

176667 269368

168285 258050

415
50542 98321 168285 258050

440 V
50680 91275 151832 234549

480 V
53313 92813 147481 213250

ECO mode

380

400

15540 23240 30956 36079

15540 23240 30956 36079

415
15540 23240 30956 36079

440 V
16131 21626 28889 37428

480 V
16853 23240 27059 36079

ECOnversion

Voltage 380

400

(V)

25% load 18683

18683

50% load 23273

23273

75% load
100% load

32629 41806

32629 41806

415
18683 23273 32629 41806

440 V
17234 20325 26436 35819

480 V
22054 23129 27059 36079

Battery operation

380

400

415

440 V

480 V

54702 95564 159938 235556

51372 95014 159521 236677

54702 95564 159938 235556

54702 95564 159938 235556

54285 96666 154530 229962

990-5451F-001

49

480 V UPS System
Options

Options

Hardware Options
· Remote maintenance bypass cabinet for UPSs up to 750 kW · Standard top cable entry battery cabinets or custom front terminal battery
cabinets · Optional remote 10­inch LCD · Optional Modbus RS-485 card

Configuration Options
· Single or dual feed · Default top or bottom cable entry · N+1 redundancy · Up to 4+1 UPSs in parallel · ECO mode · ECOnversion mode · Generator compatible · Internal synchronization to alternate source (single system) · Seismic rated brackets included · Touchscreen LCD

50

990-5451F-001

Limited Factory Warranty
Limited Factory Warranty

480 V UPS System

One-Year Factory Warranty
The limited warranty provided by Schneider Electric in this Statement of Limited Factory Warranty applies only to products you purchase for your commercial or industrial use in the ordinary course of your business.

Terms of Warranty
Schneider Electric warrants that the product shall be free from defects in materials and workmanship for a period of one year from the date of product start-up when start-up is performed by Schneider Electric-authorized service personnel and occurs within six months of the Schneider Electric shipment date. This warranty covers repairing or replacing any defective parts including on-site labor and travel. In the event that the product fails to meet the foregoing warranty criteria, the warranty covers repairing or replacing defective parts at the sole discretion of Schneider Electric for a period of one year from the shipment date. For Schneider Electric cooling solutions, this warranty does not cover circuit breaker resetting, loss of refrigerant, consumables, or preventive maintenance items. Repair or replacement of a defective product or part thereof does not extend the original warranty period. Any parts furnished under this warranty may be new or factoryremanufactured.

Non-transferable Warranty
This warranty is extended to the first person, firm, association or corporation (herein referred to by "You" or "Your") for whom the Schneider Electric product specified herein has been purchased. This warranty is not transferable or assignable without the prior written permission of Schneider Electric.

Assignment of Warranties
Schneider Electric will assign you any warranties which are made by manufacturers and suppliers of components of the Schneider Electric product and which are assignable. Any such warranties are assigned "AS IS" and Schneider Electric makes no representation as to the effectiveness or extent of such warranties, assumes no responsibility for any matters which may be warranted by such manufacturers or suppliers and extends no coverage under this Warranty to such components.

Drawings, Descriptions
Schneider Electric warrants for the warranty period and on the terms of the warranty set forth herein that the Schneider Electric product will substantially conform to the descriptions contained in the Schneider Electric Official Published Specifications or any of the drawings certified and agreed to by contract with Schneider Electric if applicable thereto ("Specifications"). It is understood that the Specifications are not warranties of performance and not warranties of fitness for a particular purpose.

990-5451F-001

51

480 V UPS System
Exclusions

Limited Factory Warranty
Schneider Electric shall not be liable under the warranty if its testing and examination disclose that the alleged defect in the product does not exist or was caused by end user or any third person misuse, negligence, improper installation or testing. Further, Schneider Electric shall not be liable under the warranty for unauthorized attempts to repair or modify wrong or inadequate electrical voltage or connection, inappropriate on-site operation conditions, corrosive atmosphere, repair, installation, start-up by non-Schneider Electric designated personnel, a change in location or operating use, exposure to the elements, Acts of God, fire, theft, or installation contrary to Schneider Electric recommendations or specifications or in any event if the Schneider Electric serial number has been altered, defaced, or removed, or any other cause beyond the range of the intended use.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF LAW OR OTHERWISE, OF PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH. SCHNEIDER ELECTRIC DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY, SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF, SCHNEIDER ELECTRIC RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS. THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE CONSTITUTE SCHNEIDER ELECTRIC SOLE LIABILITY AND PURCHASER'S EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES. SCHNEIDER ELECTRIC WARRANTIES RUN ONLY TO PURCHASER AND ARE NOT EXTENDED TO ANY THIRD PARTIES.
IN NO EVENT SHALL SCHNEIDER ELECTRIC, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE USE, SERVICE OR INSTALLATION, OF THE PRODUCTS, WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY OR WHETHER SCHNEIDER ELECTRIC HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES, SPECIFICALLY, SCHNEIDER ELECTRIC IS NOT LIABLE FOR ANY COSTS, SUCH AS LOST PROFITS OR REVENUE, LOSS OF EQUIPMENT, LOSS OF USE OF EQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA, COSTS OF SUBSTITUANTS, CLAIMS BY THIRD PARTIES, OR OTHERWISE.
NO SALESMAN, EMPLOYEE OR AGENT OF SCHNEIDER ELECTRIC IS AUTHORIZED TO ADD TO OR VARY THE TERMS OF THIS WARRANTY. WARRANTY TERMS MAY BE MODIFIED, IF AT ALL, ONLY IN WRITING SIGNED BY AN SCHNEIDER ELECTRIC OFFICER AND LEGAL DEPARTMENT.

Warranty Claims
Customers with warranty claims issues may access the SCHNEIDER ELECTRIC worldwide customer support network through the SCHNEIDER ELECTRIC web site: http://www.schneider-electric.com. Select your country from the country selection pull-down menu. Open the Support tab at the top of the web page to obtain contact information for customer support in your region.

52

990-5451F-001

Schneider Electric 35 rue Joseph Monier 92500 Rueil Malmaison France + 33 (0) 1 41 29 70 00
*990-5451F-001*
As standards, specifications, and design change from time to time, please ask for confirmation of the information given in this publication.
© 2016 ­ 2020 Schneider Electric. All rights reserved. 990-5451F-001


Servigistics Arbortext Publishing Engine PDFlib PDI 9.0.7p3 (C /Win64)